3、Polymeric
Housed MOA of Electriferous Overhaul
This product can be used to electriferous examine and repair of
substation feed-in line and overvoltage protection. It can realize
electriferous Overhaul, replacing and pre-test and reduce economic
loss because of power cutting. Technical datum meet with national
standard JB/T8952-1999 and GB11032-2000. The technical parameters
are given in Tab 2. |
|
Tab 2. Polymeric Housed
MOA of Electriferous Overhaul for 10kV system
|
Type code
|
System voltage (kV)
|
Rated voltage (kV)
|
Cont.oper.
Voltage(kV)
|
U1mAD.C≮ kV
|
Rated dischargeresidual
voltage ≯kV
|
Rectangular 2ms withstand
discharge capacity (A
|
|
YH5WS-17/50D
|
10
|
17
|
13.6
|
25
|
50
|
100
|
|
YH5WZ-17/45D
|
10
|
17
|
13.6
|
24
|
45
|
200
|
|
YH5WR-17/45D
|
10
|
17
|
13.6
|
24
|
45
|
400
|
|
|
4 Polymeric
Housed MOA of Pole Type
This product can be used to overvoltage protection.of equipments
and not only has protection fuction, but also can be used for pole
insulator. It can simplify the installation of transformer and cable
, reduce components of telegraph pole and save cost. Technical datum
meet with national standard JB/T8952-1999 and GB11032-2000. The
technical parameters are given in Tab 3.
|
|
Tab 3. Polymeric Housed
MOA of pole type for 10kV system
|
Type code
|
System voltage (kV)
|
Rated voltage (kV)
|
Cont.oper
.Voltage
(kV)
|
U1MaD.C≮ kV
|
Rated
discharge
residual voltage ≯kV
|
Rectangular 2ms withstand
discharge capacity(A
|
Perm.
bending strength
≥kN
|
Perm.
twist moment
≥Nm
|
|
YH5WS-17/50Z
|
10
|
17
|
13.6
|
25
|
50
|
100
|
1.0
|
500
|
|
YH5WZ-17/45Z
|
10
|
17
|
13.6
|
24
|
45
|
150
|
1.0
|
500
|
|
YH5WR-17/45Z
|
10
|
17
|
13.6
|
24
|
45
|
400
|
1.0
|
500
|
|
|
5 Polymeric
Housed MOA with Disconnect Device
This product can be used to overvoltage protection, especially
in neutral-point unearthing system. After long period operation
or under long time overvoltage because of single-phase earthing,
varistors will quickly deteriorate. Then Disconnect device will
act and MOA will exit operation. After they come away, they have
obvious sign and it benefits to maintain conveniently.
Technical datum meet with national standard JB/T8952-1999 and GB11032-2000.
The technical parameters are given in Tab 4.
|
|
Tab 4. Polymeric Housed
MOA with disconnect device for 6~35kV system
|
Type code
|
System voltage (kV)
|
Rated voltage (kV)
|
Cont.oper.
Voltage
(kV
|
U1mAD.C≮kV
|
Rated discharge
residual voltage
≯kV
|
Rectangular 2ms withstand
discharge capacity (A)
|
|
YH5WS-10/30L
|
6
|
10
|
8
|
15
|
30
|
100
|
|
YH5WS-17/50L
|
10
|
17
|
13.6
|
25
|
50
|
100
|
|
YH5WZ-17/45L
|
10
|
17
|
13.6
|
24
|
45
|
150
|
|
YH5WR-17/45L
|
10
|
17
|
13.6
|
24
|
45
|
400,600
|
|
YH5WZ-53/134L
|
35
|
53
|
41
|
75
|
134
|
400,600
|
|
|
|